Installation
1–32 975-0639-01-01 Rev A
This guide for use by qualified personnel only
Multiple Unit Configuration
The Conext SW inverter/chargers support multiple unit configuration to increase
power output. This gives the system engineer and/or installer more options to
work with when tailoring a system to meet load demands.
In a multiple unit configuration, only two Conext SW inverter/chargers of the same
model can be used. For example, two Conext SW 4024 120/240 units can be
configured because both units each have a 24-volt rating and a continuous
power rating of up to 3500 watts.
In this configuration, the inverter and charger capacity of a system is doubled. In
the case of two Conext SW 4024 120/240 units, the inverter power rating doubles
to 7000 watts and the charging output current doubles to 180 amps. However,
the AC transfer relay rating of 30-amps remains the same. Inverter/chargers can
operate from different battery banks, meaning each unit is connected to its own
battery bank. However, it is highly recommended to use only a single battery
bank. See “DC Connections for Multiple Unit Configuration” on page 1–33.
Figure 1-16 Multiple Unit Configuration Using Two Conext SW Units
ConextSW-NA-InstallationGuide.book Page 32 Thursday, December 20, 2012 2:05 PM