3–6 975-0639-01-01
This guide for use by qualified personnel only
Figure 3-4 Dual-Inverter System Renewable Energy (Solar) Wiring
L1
L2
Inverter
AC Distribution Panel
NEUTRAL
GROUND
Neutral
HOT L1
HOT L2
Ground
AC LEGEND
AC Cable
Solar Charge Controller
BATT
+
BATT
PV
PV
+
System Control
Panel (optional)
Renewable
Energy
Vented Battery
Enclosure
Battery Temperature Sensor
(BTS)
24-volt Battery Bank Enclosure
xantrex
Bypass
GEN
GRID
H
a
n
d
l
e
I
n
t
e
r
l
o
c
k
Bypass INV 1 OUT
INV IN
AC Breakers
Bypass
Utility
Grid
Grounding
Electrode
Conductor
Main
AC Distribution
Panel
H
a
n
d
l
e
I
n
t
e
r
l
o
c
k
Conext SW DC Switchgear
DC Disconnect
CC
+
Battery
Negative
Battery
Positive
Xanbus Stacking REM BTS
Photovoltaic
DC
Combiner Box
Negative (–)
Positive (+)
Ground
DC LEGEND
DC Cable
N
120/240 Vac or
240 Vac only
AC Generator
Conext SW Inverter/Charger
Conext SW AC Switchgear
Negative (–)
Positive (+)
BATTERY
LEGEND
Ground
Bus Bar
Neutral-to-Ground
Bond inside.
NOTE: Be sure to check the
generator for a neutral-to-
ground bond and remove it.
There can only be one neutral-
to-ground bond in the system.
System Control Panel
Ente
r
Exit
Fault/Warning
System Status
Battery 20.4 A 53.9V
BatLev E --F
Load 1235W
AC 1 115 W 3202V
Menu
Standby
12: 00 AM Jan 01
INV OUT
Xanbus
Network
Terminator
Generator
Disconnect
G
N
L2
L1
This AC Switch is a
customer-supplied
component.
AC Switch
Battery
System
Ground
Connect to
inverter’s
Chassis
Bonding
Lug
The actual positions of the Neutral bus and the Ground bus may be different than what is shown here. This drawing is for illustration purpose only.
NOTE: If no Grid is
available, the generator
can be connected to
the AC breakers in the
Conext SW AC
Switchgear, instead of
to a separate AC
Generator Disconnect.
The actual positions of the
Negative shunt and Ground bus
may be different than what is
shown here. This drawing is for
illustration purpose only.
Install a DC breaker
on the positive line.
Automatic Generator
Start (optional)
Xanbus
Network
Terminator
Power
Generator On
Network
Fault
Automatic Generator Start
Conext ComBox
(optional)
Communication Cable
(Category 5)
BTS
ACCESSORIES
ConextSW_IG_3_Wiring Diagrams_11x16p6.fm Page 6 Wednesday, December 19, 2012 2:21 PM