Redline
D.13
Pulsar S
A
B
C
D
E
F
G
X
Performance
PLS + PLS + C
(4)
PLS + 16 PLS + 32
PLS + SA & SB
PLS + PU 16 PLS + C 16 PLS + C 32
Rated current (acc. to IEC 669-2-3)
250VAC (1 & 2 pole) / 400VAC (3 & 4 pole) A 16 32 16 16 16 32
Direct Current (at 30 VDC) A 16 16 16 16 16 16
Number of poles 1 → 41 → 4 2 1 → 41 → 31 → 3
Contacts
NO 1 → 41 → 4 2 1 → 41 → 31 → 3
Changeover ("m") 1 → 4- -1 → 41 → 3-
NO + NC 1+1 / 2+2 - - 1+1 / 2+2 - -
Width (in 17.8mm DIN modules)
1 P Mod. 1 1 - 1 1 1
2 P Mod. 1 1 1 1 1½ 1½
3 P Mod. 2 2 - 2 2 2
4 P Mod. 2 2 - 2 - -
Coil specifi cations
Supply voltage : DC/AC ratio
(1)
0.5 / 1 0.5 / 1 0.5 / 1 0.5 / 1 0.5 / 1 0.5 / 1
Supply voltage range (in % of Un) % 90-110 90-110 90-110 90-110 90-110 90-110
Coil pick-up power (AC) 1P & 2P VA 14.5 16.0 14.5 4.8 14.5 14.5
3P & 4P VA 14.5 16.0 - 8.0 16.0 16.0
Coil power loss - AC 1P & 2P VA 11.0 11.5 11.0 3.2 11.0 14.5
3P & 4P VA 11.0 11.5 - 6.0 11.0 16.0
Coil power loss - DC 1P & 2P W 7.5 8.0 7.5 2.9 12.5 12.5
3P & 4P W 7.5 8.0 - 5.4 14.5 14.5
Maximum coil holding voltage time
(2) (2) (2)
unlimited
(2) (2)
Impulse times
Minimum impulse time (under Un) sec. 0.050 0.050 0.050 0.050 0.100 0.100
Minimum impulse time (90% Un) sec. 0.100 0.100 0.100 0.100 0.100 0.100
Minimum time between impulses sec. 0.150 0.150 0.150 0.150 0.150 0.150
Maximum number of impulses per mn 250 250 250 250 250 250
Lifetime (in number of operations)
(3)
Electrical (in AC-1 - At full load)
(4)
4 x 10
5
3 x 10
5
3 x 10
5
2 x 10
5
4 x 10
5
3 x 10
5
Mechanical 2 x 10
6
2 x 10
6
2 x 10
6
1 x 10
6
2 x 10
6
2 x 10
6
Load specifi cations
Maximum load AC-1 per phase A 20 32 20 20 20 32
Maximum load DC (30VDC) A 16 16 16 16 16 16
Minimum load per phase (under 5V) W 2 2 2 2 2 2
Short-circuit fuse protection A 20 32 20 20 20 32
Maximum lamp load (10
3
operations/h)
Incandescence & halogen (40 to 200 W lamps) W 3,000 4,000 3,000 3,000 3,000 4,000
Fluorescence, compensated (cos
ϕ
= 0.9)
Serial compensation VA 3,000 4,000 3,000 3,000 3,000 4,000
Parallel compensation VA 2,500 3,200 2,500 2,500 2,500 3,200
Fluorescence, non compensated (cos
ϕ
= 0.5)
VA 1,800 2,200 1,800 1,800 1,800 2,200
Maximum number of push-buttons
Non illuminated push-buttons unlimited unlimited unlimited unlimited unlimited unlimited
Luminous push-buttons (0.6mA)
4 terminals unlimited unlimited unlimited unlimited unlimited unlimited
3 terminals Without compensator 8 8 8 6 8 8
1 compensator 18 18 18 15 27 27
2 compensators 45 45 45 38 43 43
General specifi cations
Power contact add-on yes yes no no no no
Auxiliary contact add-on (PLS / CTX R) yes yes no yes yes yes
Need for spacer
(2)
yes yes yes no yes yes
DIN rail mounting yes yes yes yes yes yes
2-position DIN rail lock yes yes yes yes yes yes
2-position handle yes yes no yes yes yes
Indicator of contact position yes yes yes yes yes yes
Clamping terminals yes yes yes yes yes yes
Unlosable screws yes yes yes yes yes yes
Sealable terminals (coil and load) yes yes yes yes yes yes
Cable cross section (Ø min/max) Coil mm² 1.5 / 10 1.5 / 10 1.5 / 10 1.5 / 10 1.5 / 10 1.5 / 10
Load 1P-3P & 4P mm² 1.5 / 10 1.5 / 10 1.5 / 10 1.5 / 10 1.5 / 10 1.5 / 10
Load 2P mm² 1.5 / 10 1.5 / 10 1.5 / 10 1.5 / 10 1.5 / 6 1.5 / 10
Maximum torque on terminals Nm 1 1 1 1 1 1
Ambient temperature at installation point (min./max.) °C -20 / +45 -20 / +45 -20 / +45 -20 / +45 -20 / +45 -20 / +45
(1) For all impulse relays, DC supply voltage = AC supply voltage x DC/AC ratio, except for 8 VAC and 115VAC (48 VDC)
(2) Whenever the normal use of the impulse relay integrates a permanent coil working, use of a spacer is required on both sides. Make sure that the duty
factor allows the device to come back to the ambient temperature (not required for PLS PU)
(3) 1 cycle = 2 operations per pole (closing + opening)
(4) For any central command installation, a PLS SG module per phase must be installed in order to protect the coils against overvoltages